Summary
BGIS SCAF recommendations for Newfoundland and Labrador (Avalon Region): replace circuit breakers and panels 1E, 1F, 1G, 1H, 1J, 2F, BA and panel AA (elevator circuit breaker) due to insufficient short‑circuit ratings; apply CSA C22.1‑24 arc‑flash labelling and update Panel AA nameplate interrupting rating.
From the notice
Per SCAF dated March 2025; Equipment must, as a minimum, be labelled for arc flash hazards per CSA C22.1-24 Clause 2-306 (1) & (2). Recommend replacing the circuit breakers and panels 1E, 1F, 1G, 1H, 1J, 2F, BA and panel AA(elevator circuit breaker) due to insufficient short circuit fault ratings. Recommend having the interrupting rating on Panel AA nameplate once the replacement of the breakers has been implemented.